This article describes the connection and setup of the Motorelli AD900 Variable Speed Drive to the Polar Monitoring Gateway.
Steps to follow:
- Connect power to the Gateway.
- Connect RS-485.
- Final checks.
- Power on the system.
- Configure the Motorelli AD900 Serial Parameters.
Motorelli AD900 Connection Setup
![Connection Setup E](https://www.polarmonitoring.com/wp-content/uploads/2024/02/MOTORELLI-EXTERNAL-CONNECTION-3.png)
![Connection Setup I](https://www.polarmonitoring.com/wp-content/uploads/2024/02/MOTORELLI-INTERNAL-CONNECTION-4.png)
1. Connect power to the Gateway.
A. Power the gateway from the external power supply.
![](https://www.polarmonitoring.com/wp-content/uploads/2024/02/MOTORELLI-EXTERNAL-CONNECTION-3.png)
Wire the Polar Gateway to a 12-24 V DC power supply. Connect the positive wire to the positive terminal and the negative wire to the negative terminal.
B. Power the gateway from the VSD.
![](https://www.polarmonitoring.com/wp-content/uploads/2024/02/MOTORELLI-INTERNAL-CONNECTION-4.png)
Wire the Polar Gateway directly to the VSD. Connect the positive wire to the (+24V) terminal and the negative wire to the (COM) terminal.
2. Connect RS-485.
![](https://www.polarmonitoring.com/wp-content/uploads/2024/02/MOTORELLI-EXTERNAL-CONNECTION-3.png)
Wire the RS-485 cable to allow communication with the Polar Gateway. Connect A+ to 485+terminal,B- to 485- and G to PE. What is RS-485?
3. Final checks
- Make sure the wiring is secure – no short circuits.
- Ensure that all connections are secure on the device and the gateway.
- Re-check the RS-485 twisted pair cable is correctly wired.
- Check that the A and B are correctly wired to the device.
4. Power on the system
Now you are ready to go, you can now switch on the Polar Gateway and the Motorelli AD900.
5. Configure Motorelli AD900 Serial Parameters
Serial Communication Setup
Name | Description | Parameter | Default | Required |
Serial Address | Serial Slave ID | P14.00 | 1 | 1 |
Serial Baud Rate | Baud Rate | P14.01 | 4 = 19200 | 3 = 9600 |
Serial Bytes Config | Communication settings | P14.02 | 1 = 8 bits, even, 1 | 0 = 8 bits, no, 1 |
Serial Protocol | Communication protocol | P00.02 | 0 = Modbus RTU | 0 = Modbus RTU |
Remote Control Setup
Name | Description | Parameter | Default | Required |
LOC/REM Selection | What source will determine if the device is in REM/LOC mode. | P00.01 | 0 | 2 |
REM Reference Sel. | Speed / frequency reference source when in remote mode | P01.O1 | 0 | 0 |
REM Run/Stop Sel. | Start/Stop Command Source when in remote mode. | P01.00 | 0 | 0 |
You may now sign in to the Polar Portal to monitor the device remotely, the button on the right will take you through a setup process.