Delta ME300 Variable Speed Drives

This guide will show you how to connect the Polar Monitoring Gateway to the Delta ME300 Variable Speed Drive. It will also take you through the setup and parameters required on the ME300 to ensure communications to the Polar Gateway, in order to control, program, and monitor your device remotely.

Steps to follow:

  1. Connect power to the Gateway.
  2. Connect RS-485.
  3. Final checks.
  4. Power on the system.
  5. Configure the ME300 Serial Parameters.
 

Delta ME300 Connection Setup

1. Connect power to the Gateway.
A. Power the gateway from an external power supply.
Power Polar Gateway

Wire the Polar Gateway to a 12-24 V DC power supply. Connect the positive wire to the positive terminal and the negative wire to the negative terminal.

B. Power the gateway from the VSD.

Wire the Polar Gateway directly to the VSD. Connect the positive wire to the +24V terminal and the negative wire to the DCM terminal.

2. Connect RS-485.
Delta ME300 RS-485 to Polar

Wire the RS-485 cable to allow communication with the Polar Gateway. Connect A+ => SG+ (5) and the B- => SG- (4). What is RS-485?

3. Final checks
Before switching on the Gateway and the device, make sure you have completed all the previous steps correctly.
 
  • Make sure the wiring is secure – no short circuits.
  • Ensure that all connections are secure on the device and the gateway.
  • Re-check the RS-485 twisted pair cable is correctly wired.
  • Check that the A and B are correctly wired to the device.
4. Power on the system

Now you are ready to go, you can now switch on the Polar Gateway and the Delta ME300.  

5. Configure Delta ME300 Serial Parameters
In order for the Gateway to correctly communicate with the ME300 controller, there will need to be some changes made to the communication parameters. 

Note: It is critical to change the default settings to reflect the table below.

Serial Communication Setup

NameDescriptionParameterDefaultRequired
Communication AddressDevice ID/Unit ID/Node ID09-0011
Baud RateCommunication Speed09-019.69.6
COM1 ProtocolCommunication protocol and Data Format09-041=7, N, 2 (ASCII)12=8, N, 1 (RTU)

Remote Control Setup

Modbus registers can be edited and monitored remotely, but to enable remote control of the variable speed drive the below registers must be set accordingly.

Name DescriptionParameter 
DefaultRequired 
Operation Command Source (AUTO, REMOTE)Determines the operation frequency source in the “AUTO, REMOTE” mode.00-2102
Master Frequency Command Source (AUTO, REMOTE) Determines the master frequncy source in the “AUTO, REMOTE” mode.00-2102
LOCAL/REMOTE selectionDetermines the mode selection.00-2904

You may now sign in to the Polar Portal to monitor the device remotely, the button on the right will take you through a setup process.