LS ELECTRIC S100 Variable Speed Drives
This guide will show you how to connect the Polar Monitoring Gateway to the LS ELECTRIC S100 Variable Speed Drive. It will also take you through the setup and parameters required on the LS ELECTRIC S100 to ensure communications to the Polar Gateway.
Steps to follow:
- Connect power to the Gateway.
- Connect RS-485.
- Final checks.
- Power on the system.
- Configure the LS ELECTRIC S100 Serial Parameters.
LS ELECTRIC S100 Connection Setup
1. Connect power to the Gateway.
A. Power the gateway from an external power supply.
Wire the Polar Gateway to a 12-24 V DC power supply. Connect the positive wire to the positive terminal and the negative wire to the negative terminal.
B. Power the gateway from the VSD.
Wire the Polar Gateway directly to the VSD. Connect the positive wire to the +24V(24) terminal and the negative wire to the (EG) terminal.
2. Connect RS-485.
Wire the RS-485 cable to allow communication with the Polar Gateway. Connect A+ => S+ and the B- => S- . What is RS-485?
3. Final checks
- Make sure the wiring is secure – no short circuits.
- Ensure that all connections are secure on the device and the gateway.
- Re-check the RS-485 twisted pair cable is correctly wired.
- Check that the A and B are correctly wired to the device.
4. Power on the system
Now you are ready to go, you can now switch on the Polar Gateway and the LS ELECTRIC S100.
5. Configure LS ELECTRIC S100 Serial Parameters
Note: It is critical to change the default settings to reflect the table below.
Serial Communication Setup
Name | Description | Parameter | Default | Required |
Communication Address | Device ID/Unit ID/Node ID | Int485 St ID | 1 | 1 |
Serial Speed | Communication Speed | Int485 BaudR | 3=9600 | 3=9600 |
Data Format | Stop bit, Data bits and parity | Int485 Mode | 0=D8/PN/S1 | 0=D8/PN/S1 |
Protocol | Communication protocol | Int485 Proto | 0=Modbus RTU | 0=Modbus RTU |
Remote Control Setup | ||||
Name | Description | Parameter | Default | Required |
LOCAL/REMOTE Selection Source | Set dr.90 to 2(Local/Remote)to perform | dr.90 | 2=local/ remote | 2=local/ remote |
local/remote switching using | ||||
the [ESC] key | ||||
Fwd/Rev run | command source | drv-06 | 1=Fx/Rx-1 | 1=Fx/Rx-1 |
You may now sign in to the Polar Portal to monitor the device remotely, the button on the right will take you through a setup process.