This guide will show you how to connect the Polar Monitoring Gateway to the Lovato DMG700-900 Power Analyzer. It will also take you through the setup and parameters required on the Lovato DMG700-900 to ensure communications to the Polar Gateway.
Steps to follow:
- Connect power to the Gateway.
- Connect RS-485.
- Mount the EXP 1020 to the module expansion slot.
- Final checks.
- Power on the system.
- Configure the DMG700-900 Serial Parameters
Lovato DMG700-900 Connection Setup
![Lovato DMG700-900- Wiring Diagram](https://www.polarmonitoring.com/wp-content/uploads/2022/08/Lovato-DMG700-900-Wiring-Diagram-756x1024.png)
1. Connect power to the Gateway.
![Power Polar Gateway](https://www.polarmonitoring.com/wp-content/uploads/2022/08/Power-Polar-Gateway.jpg)
Wire the Polar Gateway to a 12-24 V DC power supply. Connect the positive wire to the positive terminal and the negative wire to the negative terminal.
2. Connect RS-485
![RS-485 Connection](https://www.polarmonitoring.com/wp-content/uploads/2022/08/Lovato-DMG700-900-Gateway.png)
![RS-485 Connection](https://www.polarmonitoring.com/wp-content/uploads/2022/08/Lovato-DMG700-900.png)
Wire the RS-485 cable to allow communication with the Polar Gateway. Connect A+ => A and the B- => B.
3. Mount the EXP 1012 to the module expansion slot.
![](https://www.polarmonitoring.com/wp-content/uploads/2023/01/DMG700-900-Back-view.png)
Open any of the four available module expansion slots of the DMG700-900 and clip in the EXP 1012 RS-485 communication module.
4. Final checks
- Make sure the wiring is secure – no short circuits.
- Check if the power cables are not loosely wired to the Gateway.
- Check if the power cables are not loosely wired to the device.
- Make sure the RS-485 module is correctly mounted on the device.
- Re-check the RS-485 twisted pair cable is correctly wired.
5. Power on the system.
Now you are ready to go, you can now switch on the Polar Gateway and the DMG700-900.
6. Configure DMG700-900 Serial Parameters
Note: It is critical to change the default settings to reflect the table below.
Serial Communication Setup
Name | Description | Parameter | Default | Required |
Communication Address | Device ID/Unit ID/Node ID | P07.n.01 | 1 | 1 |
Baud Rate | Communication Speed | P07.n.02 | 9600 | 9600 |
Data Format | Data length and parity check | P07.n.03 | 8 bit – n | 8 bit – n |
Stop bit | End of data transmission | P07.n.04 | 1 | 1 |
Protocol | Communication protocol | P07.n.05 | Modbus RTU | Modbus RTU |
You may now sign in to the Polar Portal to monitor the device remotely, the button on the right will take you through a setup process.